Page 32
9130 UPS-EN
7. Specifications
Table 18. Electrical Input
Model Default Input
(Voltage/Current)
Selectable Input
Voltage Range
Voltages
at 100 % Load
PW9130i5000T-XL 230 V / 21.7 A 200*, 208*, 220, 230, 240 180–276 Vac
PW9130i6000T-XL 230 V / 26.1 A 200*, 208*, 220, 230, 240 180–276 Vac
208 V are derated by 10 %.
Table 19. Electrical Input Connections
Model Input Connection Input Cable
PW9130i5000T-XL
PW9130i6000T-XL
Hardwired None
Table 20. Electrical Output
All Models Normal Mode Battery Mode
Voltage Regulation ±2 % Nominal output voltage ±3 %
Efficiency > 98 % (High Efficiency mode),
> 94 %
> 92 %
Frequency Regulation Sync with line ±3 Hz of nominal line
frequency (outside this range: ±0.1 Hz
of auto-selected nominal frequency)
±0.1 Hz of auto-selected nominal
frequency
High Voltage Models
Nominal Outputs 200/208/220/230/240V (voltage configurable or auto-sensing)
5000/6000 VA 4.5/5.4 kW
Frequency 50 or 60 Hz, autosensing or configurable as a frequency converter
Output Overload 100–102 %: Activates Overload alarm (Level 1)
102–129 %: Load transfers to Bypass mode after 2 minutes (Level 2)
130–149 %: Load transfers to Bypass mode after 30 seconds (Level 3)
≥ 150 %: Load transfers to Bypass mode after 100 ms (Level 4)
Output Overload
(Bypass Mode)
100–109 %: Activates Overload alarm (Level 1)
110–129 %: UPS shuts down after 5 minutes (Level 2)
130–149 %: UPS shuts down after 30 seconds (Level 3)
≥ 150 %: UPS shuts down after 300 ms (Level 4)
Voltage Waveform Sine wave
Harmonic Distortion < 3 % THD on linear load;
< 5 % THD on non-linear load
Transfer Time Online mode: 0 ms (no break)
High Efficiency mode: 10 ms maximum (due to loss of utility)
Power Factor 0.9
Load Crest Factor 3 to 1
Table 21. Electrical Output Connections
Model Output Connections Output Cables
PW9130i5000T-XL
PW9130i6000T-XL
Hardwired None